4zones
Conventional Fire Alarm Control Panel /Security Alarm Host/ Master
Control Panel
Products Features
4,8,*6
Class B Initiating Device Circuits (IDCs)
✓ All zones accept conventional detectors and any normally
open contact device
ï¬ Four Class B Notification Appliance Circuits (NACs)
ï¬ One Form-A Alarm Relay
ï¬ One Form-A Trouble Relay
ï¬ One Form-A Supervisory Relay
ï¬ 3.0 amps of system power
ï¬ Max *0 conventional detectors in one zone.
ï¬ Auto/Manual mode setting enable walk test.
ï¬ Each Zone can be disabled,
ï¬ Sound output can be disabled.
ï¬ Manual active sound output enabled.
ï¬ Able to report short and broken circuit of detection
zones.
ï¬ Designed with standby batteries and space provision for two
sealed lead-acid batteries.
ï¬ Testing and disable functions.
ï¬ Can connect max *2 repeater panels by RS**5 communication
port
ï¬ Dimensions : *4.*7 " (*7 cm) long X *7.*2" (*4 cm) high X
3.*4"(*0cm).
ï¬ Weight: 6.6kg (without battery).
Specifications
AC Power
*****0 VAC, *0 Hz, 2.3 amps
Wire size: minimum #*4 AWG (2.0 mm 2 ) with **0V insulation
Battery (lead acid only)
Maximum Charging Circuit: Normal Flat *—*@********************
Maximum Charger Capacity: *8 Amp Hour batter
Sound Output Device Circuits
General Alarm Zones 1 through *6
Operation: All zones Class B
Normal Operating Voltage: Nominal *4 VDC (ripple = **0 mV
maximum)
Alarm Current: *5 mA threshold
Short Circuit Current: *2 mA maximum
Maximum Loop Resistance: **0 ohms
End-of-Line Resistor: 4.7K, ½ watt
Detector Loop Current is sufficient to ensure operation of two
alarmed detectors per zone
Standby Current: 7.*6 mA
Three Relays Output
Relay contact rating: 2.0 amps
País: | China |
N º de Modelo: | ck1004/1008/1016 |
Precio FOB: | 140 ~ 170 / Piece ( Negotiable ) Obtener el precio más reciente |
Lugar de origen: | china |
Precio de pedido mínimo: | 140 per Piece |
Cantidad de pedido mínimo: | 1 Piece |
Detalle de embalaje: | netural packing |
El tiempo de entrega: | 5~7days for small order, for bigger order, it depen |
Capacidad de suministro: | 10000 Piece per Month |
Tipo de pago: | PayPal, Western Union, T/T |
Grupo de productos : | conventional fire alarm system |