RFQ Details

Requirement: Radiator for gas engine of following specification.
LT Circuit:
Fluid - Water
Normal heat dissipation - 1255 kW
Required heat dissipation - 1630 kW (1255 kW + 20% safety + 10% fouling)
Normal flow- 100 m3/h
Maximum flow - 144 m3/h
Cooler inlet temp. - 59.9 degC
Cooler outlet temp. - 48 degC
Allowable pressure drop at normal flow - 43 kPa
Allowable pressure drop at maximum flow - 82 kPa
Internal liquid volume - 434 liters
Connection flange - DN100
Fin pitch - 4.0 mm
No. of tube rows - 5

HT Circuit:
Fluid - Water
Normal heat dissipation - 625 kW
Required heat dissipation - 750 kW (625 kW + 10% safety + 10% fouling)
Normal flow- 32 m3/h
Maximum flow - 86 m3/h
Cooler inlet temp. - 90 degC
Cooler outlet temp. - 68.9 degC
Allowable pressure drop at normal flow - 4 kPa
Allowable pressure drop at maximum flow - 25 kPa
Internal liquid volume - 93 liters
Connection flange - DN80
Fin pitch - 4.0 mm
No. of tube rows - 1

Other requirements:
No. of coolers - 2 (each sharing LT & HT equally)
Maximum operating temp. - 100 degC
Operating pressure - 10 barg
Design pressure - 15 barg
Casing material - Galvanized steel
Tube material - Copper
Fin material - Aluminium
No. of fans per cooler - 5 (minimum 4)
Maximum length - 10 m
Maximum width - 2.4 m
Maximum height (without leg support) - 1.6 m
Maximum height (with leg support) - 3.6 m
Sound level at 10 m - 66 dB(A) for 1 cooler
Sound level at 10 m - 69 dB(A) for 2 coolers

Inputs: 3 phase/400V/50Hz
Ambient air temp. - 40 degC
Power supply - 3 phase, 400 V, 50 Hz

Requested to send a quotation.